2 Installation of Racks 5
Chapter 2
Installation of Racks
Mounting the Rack
ESR3-12 racks are normally wall-mounted.
ESR3-24 racks can be mounted to a wall or floor-mounted on an optional pedestal.
ESR3-36 and ESR3-48 racks are floor standing.
Mounting Racks on a Wall (ESR3-12 and ESR3-24)
The wall must be strong enough to hold the racks. Please see Appendix A: Sensor3 CE
Rack Specifications, page 34 for rack and module weights.
Step 1: Determine where your rack will be installed using Figure 1: Sensor3 rack
clearances on page 4 and use the appropriate diagram from Figure 2 to mark
your mounting holes.
Step 2: Use the mounting slot dimensions to mark the hole locations. You must supply
your own M10 mounting hardware.
Step 3: Drill the holes and install the hardware.
Step 4: Attach the rack to the wall.
Figure 2: ESR3-12 and ESR3-24 wall mount hole diagrams